FLK-1662 SCH, Multifunction Installation Tester 1GOhm IP40, Fluke

Product Code: 4546944
no gallery
no gallery
FLUKE
Brand
More similar products

Price range

AmountPrice with tax (pcs)
1+
-8%
1,547.601,424.20
wholesale

Min. qty: 1

Unit: pcs

Total:

1,424.20
Pirkite už 50 € ar daugiau ir
atsiskaitykite su

Delivery terms

lemona shop

Pickup In Store

Pickup In Store For free

Orders are processed and shipped on weekdays from 8:00 a.m. to 5:00 p.m. When your order is ready for collection, we will inform you by SMS and e-mail.

Quantity in shop

Not availableNot available
Vilnius Žirmūnai Store
Not availableNot available
Vilnius Naujamiestis Store
Not availableNot available
Kaunas Store
Not availableNot available
Klaipėda Store
Not availableNot available
Šiauliai Store
Not availableNot available
Central Warehouse (new location)
home delivery

Home delivery in Lithuania

Home delivery in Lithuania

After handing over the goods to the courier, we will inform you by e-mail. If you are ordering outside of Lithuania please use www.lemona-electronics.eu to order.

Over €50.00

(Orders up to 1000 kgs)

For free

To €50.00

(Orders up to 3 kgs)

€3.49

To €50.00

(Orders up to 1000 kgs)

€4.99

Shipping parcel

Delivery to a DPD Pickup location

Delivery to a DPD Pickup location

After handing over the goods to the courier, we will inform you by e-mail. Orders over €50.00 are delivered free of charge.

€2.39

Product description

FLUKE
Weight
0 kg.
Brand
Warranty period (months)
24

Fluke 1662 Multifunction Tester

The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

  • Measures RCD switching time and tripping level (ramp test)
  • Measures trip time and current for RCD type A & AC in one test
  • Measures RCD variable current
  • Provides automatic RCD test sequence
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Includes a phase sequence indicator
  • Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead

Specifications: 

AC voltage measurement
Range 500 V
Resolution 0.1 V
Accuracy 45 Hz – 66 Hz 0.8% + 3
Input impedance 360 kΩ
Overload protection 660 V rms
Continuity testing (RLO)
Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage >4 V
Insulation resistance measurement (RISO)
Accuracy of test voltage (at rated test current) +10%, -0%
Test voltage 100 V
250 V
500 V
1000 V
Insulation resistance range 20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution 0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current 1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range 10 Ω / 0.001 Ω / High current mΩ mode
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Prospective earth fault current, PSC test
Range 1000 A / 10 kA (50 kA)
Resolution 1 A / 0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type A4, AC¹, G², S³
Notes ¹Responds to AC
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
Notes ¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range 30% to 110% of RCD rated current¹
Step size 10% of IΔN²
Dwell time Type G 300 ms/step
Type S 500 ms/step
Measurement accuracy ±5%
Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
²5% for Type B
Notes ¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
Phase Sequence Indication
Icon icon phase sequence indicator  Phase Sequence indicator is active.
General Specifications
Size (L x W x H) 10 x 25 x 12.5 cm
Weight (incl. batteries) 1.3 (kg)
Battery size, quantity Type AA, 6 ea.
Sealing IP-40
Safety Complies with EN/IEC 61010-1 and  EN/IEC 61010-2-034
Overvoltage CAT III / 500V; CAT IV 300V
Performance EN61557-1 to EN61557-7 and EN61557-10

Useful information


Specifications

SKU
424541
Barcodes
095969766807
Weight
0 kg.
Brand
Warranty period (months)
24
Product code
4546944

Supplier product description

Installation tester 1662 SCH (Schuko) 1X INSTALLATION TESTER,1X MAINS CORD,1X ZERO ADAPTOR,1X INFO PACK,1X HARD CASE,1X CARRY STRAP,6X AA BATTERY,1X REMOTE PROBE,1X TEST LEAD SET,1X STATEMENT OF CALIBRATION CARD, 1X SLEEVE,1X SHIPPING BOX

Useful information

The information that supplier provides may differ from the actual product. If you noticed an error please let us know by email: [email protected].